i
Never connect more than one SYMPL bridge Node in
factory state to a network. The identical IP addresses will
conflict and disturb proper communication.
4.4
DMX connection
The SYMPL bridge Node can control eight DMX / e:pix universes with its
eight DMX ports. Connect DMX / e:pix devices to the SYMPL Node using
3-pin terminal plugs at the DMX interface of the SYMPL Node.
The appropriate pin assignment is defined as follows:
From left to right: GND, DMX-, DMX+
It is recommended to use twisted pair cabling.
Use shielded cables for outdoor installations.
Ground the DMX connection cable for outdoor installations
!
(optional for indoor only). Ground each cable seperately.
4.5
Power supply
The e:cue SYMPL bridge Node can be powered by an external power
supply or via Power-over-Ethernet.
PoE:
For PoE, simply connect an Ethernet connection from a power sourcing
device.
External power supply:
Connect the SYMPL bridge Node to a certified NEC Class 2 24 V DC
power supply unit. Present power supply equates to the status "On" or
running of the SYMPL Node.
Installation
17