2 .3 .4 Unit selection

Selection of the applicable ventilation units in 3 groups:
• Ceiling unit with cross counter-flow heat exchanger (X-WT)
• Standing unit with cross counter-flow heat exchanger (X-WT)
• Standing unit with rotary heat exchanger (Rot-WT)
Only one ventilation unit can be selected. The word "None" appears automatically in the other two windows. The last
setting is valid.
Ceiling unit X-WT
Choose configuration
None
2 .3 .5 External control 0-10 V
Selection of "External 0-10 V" control. In case of external fan control, this mode must be selected if an external cont-
roller regulates the air flow.
Select Yes/No:
External 0-10V
control
No

2 .3 .6 Temperature control mode

The temperature control influences the existing heating and cooling registers:
• Electrical heating
• Warm water heating
• DX cooling
• Cold water cooling
The temperature control mode can only be set by the commissioning assistant (wizard). The following temperature
control modes are available:
a . Constant Supply Air Control
b . Outdoor Compensated Supply Air Control
c . Cascade Room Temperature Control
d . Cascade Extract Air Temperature Control
e . Outdoor Temperature Dependent Supply or Room Temperature Control
f . Outdoor Temperature Dependent Supply or Extract Temperature Control
g . Outdoor Temperature Dependent Room Temperature Control
h . Outdoor Temperature Dependent Extract Air Control
a . Constant Supply Air Control
The heating and cooling outputs can only be adjusted to the supply air sensor in Constant Supply Air Control mode. A
neutral zone can be defined for the setpoint.
Example: If the setpoint is 18 °C and the neutral zone (NZ) is 2°C: Setpoint heating = 17°C and setpoint cooling = 19°C.
If the supply air temperature is in the neutral zone "heating" and "cooling" are blocked. If the supply air temperature falls
below the setpoint -NZ/2, the "heating" mode will be active until the setpoint is reached. If the supply air temperature
rises above the setpoint +NZ/2, the "cooling" mode will be active until the setpoint is reached.
The setpoint is displayed in the "temperature" menu (log in as User or Administrator):
Temp. control mode
Supply air control
Supply air temp.
Setp: XX.X °C
Neutral zone
X.X °C
b . Outdoor Compensated Supply Air Control
The supply air temperature setpoint can be set to improve the regulation of room heat losses due to the outdoor tem-
perature. This ensures that the cooling of room walls is compensated for during the cold season.
The supply air temperature setpoint is compensated for depending on the outdoor temperature using a control curve
with 8 points.
AIR1 RH series
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
21