Installation and Operating Instructions
Compact Ventilation Units AIR1 XC
Stage 3
Deactivation of the ventilation unit (close external dampers).
Ventilation unit restart
The automatic ventilation unit restart will only take place if either the outside air temperature is higher than -3 °C or the
exhaust air temperature is higher than +4 °C.

4 .1 .2 Warm water heating register frost protection

The optional warm water heating register has frost protection with the following functionality:
100 %
15
C
O
50 %
7
C
O
0 %
Activation of frost protection:
• Below +15 °C: The valve is opened by the frost protection sensor signal; the pump cycle is started.
• Below +7 °C: Ventilation is deactivated, the external dampers close and the valve is completely opened.
Deactivation of frost protection:
• Frost protection sensor temperature above +15 °C.

4 .1 .3 Filter monitoring

The dynamic filter monitoring is used to check the filter condition. This highest possible filter pressure loss is calculated
in relation to the selected filter type and the operating point. If the filter pressure loss is greater than the permitted pres-
sure loss at this operating point, the filter alarm will be triggered.

4 .2 Priorities

If multiple ventilation modes are active at the same time, the ventilation unit will run at the respective ventilation stage
with the highest priority. This means that the external switch contact overrides all other ventilation stages.
Priority list (highest priority first):
• Fire/emergency contact
• External switch contact
• Manual operation with HMI or use of building control system (Bacnet, Modbus)
• External switch contact Intensive
• External switch contact Normal
• External switch contact Minimal
• External switch contact Recirculation
• Timer Intensive
• Timer Normal or Timer VOD with higher ventilation requirement
• Timer Minimal or Timer VOD with higher ventilation requirement
• Timer Recirculation or Timer VOD
• Free cooling (night cooling)

4 .3 User levels/Access rights

Depending on the selected operating level, different functions/menus are active via the controller.
The following user levels are available:
• No rights
• User (password: 3333)
• Service (password: 2222)
• Administrator (password: 1111)
The user levels can be modified in the "Access rights" menu. All user levels will automatically reset to "No rights" after a
pre-set time of 5 minutes from the last press of a button.
All passwords can be modified in the "Access rights" menu under "Change password".
Frost protection sensor temp.
Temperatur Frostschutzsensor
38
Fig .16
Heating valve signal
Signal Heizventil
EN