7.23 Compensation Frequency
Control according to a system curve (increase of the set pressure, depending upon the
flow rate or speed).
set pressure should be increased. That is the speed, where the pump works at the set
pressure and at a flow rate=0 (can be read in the JOG MODE).
Press
7.24 Lift-Intensity
Lift-Intensity
Figure:
Downloaded from
www.Manualslib.com
FREQU. – LIFTING
30.0 Hz
on the Hydrovar-Smart to change to
LIFT – AMOUNT
0.0 %
1. Setting of the required pressure (see: Inverter main menu)
2. Enter frequency for demand = 0 and set pressure = Actual Value
(see: Jog Mode ) ⇒ FREQU. LIFTING
3. Set desired lift at maximum speed, in % of required pressure.
manuals search engine
Adjustable between 6 Hz and the set MAXIMUM
FREQUENCY, this setting states at which frequency the
Adjustable from 0% to 99,9%; this value states how
much the set value should be increased, when the
pump is running at maximum speed (=maximum
flow).