Press
For calculation of the set pressure after start of pumps 2 to 4
Press
Pump has reached the programmed frequency (Adjustable from 0.0 Hz to 70 Hz)
If you do not want to start a following pump this value has to be set higher than the
maximum frequency.
This parameter is also used to start a constant speed pump (when Simple Multicontr. is
set). When this frequency level is reached, the potential free contact of the relay X2/5 –
X2/6 will be closed.
Press
Downloaded from
www.Manualslib.com
on the Hydrovar-Smart to change to
7.21.2 Fall Value
ACTU. VALUE DEC.
0.15 BAR
on the Hydrovar-Smart to change to
7.21.3 Release frequency of the following controller
ENABLE SEQ. CTL.
48.0 Hz
on the Hydrovar-Smart to change to
manuals search engine
Adjustable from 0,0 to pre-selected Sensor range
determines the start-value of the 2
other following pumps.
(Start-Value = REQUIRED VALUE –ACT. VALUE DEC.)
Release of the follow-up pump only when the start-
value is reached and the lead
31
nd
pump and the