Short Circuit Current Ratings (SCCR) with Semiconductor Fuses
(Tested per UL61800-5-1, reference UL file E132659)
These devices are suitable for standard installation when used with Semiconductor Fuses. For single motor
installation, if the fuse value indicated is higher than 400 % of the motor current (FLA), the fuse value has to
be calculated. If the value of the fuse is below two standard ratings, the nearest standard ratings less than
the calculated value shall apply.
Mains
230 V, 1/3-ph
230 V, 1/3-ph
230 V, 1/3-ph
230 V, 1/3-ph
230 V, 3-ph
230 V, 3-ph
230 V, 3-ph
480 V, 3-ph
480 V, 3-ph
480 V, 3-ph
480 V, 3-ph
480 V, 3-ph
480 V, 3-ph
480 V, 3-ph
480 V, 3-ph
480 V, 3-ph
480 V, 3-ph
480 V, 3-ph
480 V, 3-ph
480 V, 3-ph
480 V, 3-ph
Umrichter
Rated power
kW
0.37
0.55
0.75
1.5
2.2
4
5.5
0.55
0.75
2.2
4
7.5
11
15
22
30
45
55
75
90
110
Alternate Fuse (Semiconductor Fuse)
SCCR
HP
kA
0.5
100
0.75
100
1
100
2
100
3
100
5
100
7.5
100
0.75
100
1
100
3
100
5
100
10
100
15
100
20
100
30
100
40
100
60
100
75
100
100
100
125
100
150
100
Elektrische Installation
Anschluss nach UL
Absicherungsdaten
Max. rated current
A
6
10
16
25
35
63
80
6
6
20
35
63
80
80
100
125
125
200
200
350
350