Electrical installation
Networks

EtherNet/IP

EtherNet/IP
Connection status
The LEDs at the RJ45 sockets show the connection status to the network:
LED "link" (green)
Off
On
LED "Activity" (yellow)
Off
On or flashing

Network status

The "NS" and "MS" LEDs display the network status.
LED "NS" (green/red)
off
On (green)
Blinking green
Blinking red
on (red)
Blinking green/red
LED "MS" (green/red)
off
On (green)
Blinking green
Blinking red
on (red)
Blinking green/red
162
State/meaning
Not connected to network.
Physical connection to network available.
State/meaning
No data transfer.
Data is being exchanged via the network.
CIP network status
No IP address
Connected
No connections
Connection timeout
Duplicate IP
Device self testing
CIP module status
Nonexistent
Operational
Standby
Major recoverable fault
Major unrecoverable fault The network option contains a non-correctable error.
Device self testing
Status/meaning
The network option is not supplied with voltage or has not received an
IP address yet.
The network option is working correctly and has established a
connection to the scanner.
The network option
• works correctly,
• has been assigned to an IP address,
• has not been implemented into the network yet by the scanner.
A time-out has occurred.
The network option cannot access the network (IP address conflict).
The network option executes a self-test.
Status/meaning
The network option is not supplied with voltage.
The network option works correctly.
The network option is not configured completely or the configuration is
incorrect.
The network option contains a correctable error.
The network option executes a self-test.

Werbung