Motor holding brake connection

The inverter is designed for 24 V brakes. A motor holding brake is connected to X106 and supplied via X107.
DANGER!
Loss of the safe isolation
Safe isolation of the control card from the mains potential is deactivated when the motor and motor holding
brake are connected via a system cable AND X5 and X107 are supplied by a common power supply unit. This
also applies when using a SELV/PELV power supply unit.
Possible consequences: Electric shock in the event of a fault.
▶ Supply X107 and X5 by separate SELV/PELV power supply units if the motor and motor holding brake are
connected via a system cable.
X107 and X5 can be supplied by a common SELV/PELV power supply unit if the motor and motor
holding brake are connected via safely isolated installed cables.
Fig. 15: Connection diagram - motor holding brake
Motor holding brake connection
Terminal
Level
Max. Output current
Cycle time
Short-circuit-proof
Suppressor circuit
Max. Breaking energy
Max. Switching rate
Insulation
DC 24 V SELV/PELV
(+19.2 V ... +28.8 V)
n
EYF
X106: temperature connection
T1 / T2 BD1, BD2
V
LOW: < +5, HIGH: > +15
0.37 ... 15 kW A
2.5
22 ... 110 kW
5.0
ms
1
Unlimited period
Integrated freewheeling diode
and spark suppressor
0.37 ... 15 kW Ws
5
22 ... 110 kW Ws
20
6/min. at max. output current
Basic insulation
Double/reinforced insulation
Electrical installation
Motor holding brake connection
Controlling a motor holding brake with or
without brake voltage reduction
Depending on the output current:
Switching frequency doubles if the output
current is halved
Connection via system cable
Connection via separated cable