U10M, U10S
The cable shield is connected with the transducer housing. Only use plugs
that meet EMC guidelines. The shielding must be connected extensively. With
other connection techniques, an EMC-proof shield should be applied in the
wire area and this shield should also be connected extensively (see also HBM
Greenline Information, brochure i1577).
6.2 Connection with four-wire configuration
When transducers with a six-wire configuration are connected to amplifiers
with a four-wire configuration, the sense leads of the transducer must be con-
nected to the corresponding supply leads: Identification (+) with (+) and identi-
fication (−) with (−), see Fig 6.1. This measure also reduces the cable resist-
ance of the excitation voltage leads. However, there will be a voltage loss on
the supply leads due to the cable resistance that is still present and not com-
pensated for by the six-wire configuration. A large part of this loss can be
eliminated by a calibration, however, the temperature-dependent part remains.
The TK
value given in the specifications for the transducer therefore does not
c
apply for the cable and transducer combination when connection is with four-
wire configuration, the cable percentage must be added.
6.3 EMC protection
Electrical and magnetic fields often induce interference voltages in the mea-
suring circuit. Therefore:
• Use shielded, low-capacitance measurement cables only (HBM cables
fulfill both conditions).
• Do not route the measurement cables parallel to power lines and control
circuits. If this is not possible, protect the measurement cable with e. g. steel
conduit.
• Avoid stray fields from transformers, motors and contact switches.
• Do not ground the transducer, amplifier and indicator more than once.
• Connect all devices in the measurement chain to the same grounded
conductor.
• Always connect the cable shield extensively to the connector housing.
A1385−6.0 en/de/fr
23
HBM