5.3.4 Voltage supply / supply network connection

T
T
DANGER
Danger to life due to incorrect connection.
Residual current circuit breaker (type B) sensitive to uni-
versal currents may not installed behind residual current
circuit breaker (type A) sensitive to pulse currents. Note the
following points when connecting to the power supply:
f Observe DIN VDE 0100, part 530.
f Make sure that the charging system is not installed
behind residual current circuit breaker (type B) sensitive
to pulse currents.
f Please comply also with local requirements.
Note the following points when connecting to the power
supply:
„ This device may be installed, commissioned and ser-
viced only by a qualified electrician in accordance with
relevant national regulations; see Chapter "2.1 Target
groups".
„ Before connecting the device, caution must be taken to
ensure that it is free of voltage or the appropriate pro-
tective measures have been taken.
The charging column may be connected only to a TN-S
system.
Fig. 18: Terminal block in charging column
Connect the supply line:
f Connect the foundation earth electrode to the earthing
point in the charging column according to DIN 18014.
f Connect the supply line according to the terminal label-
ling (for tightening torque, see the Chapter "4. Technical
Data").
f Check that the individual cores are connected correctly
and that the screws are tightened.