Herunterladen Inhalt Inhalt Diese Seite drucken

Motor Connection; Environmental Conditions; Electrical Supply Conditions - Lenze i550 Montage- Und Einschaltanleitung

0.25 kw ... 132 kw 0.5 hp ... 175 hp
Vorschau ausblenden Andere Handbücher für i550:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Motor connection

Requirements for the shielded motor cable
Capacitance per unit length
C-core-core/C-core-shielding < 75/150
pF/m
C-core-core/C-core-shielding < 150/300
pF/m
Electric strength
Uo/U = 0.6/1.0 kV
U ≥ 600 V

Environmental conditions

Energy efficiency
Class IE2
Climate
1K3 (-25 ... +60°C)
2K3 (-25 ... +70°C)
3K3 (-10 ... +55°C)
Site altitude
0 ... 1000 m amsl
1000 ... 4000 m amsl
Pollution
Degree of pollution 2
Vibration resistance
Transport
2M2 (sine, shock)
Operation
Amplitude 1 mm
Acceleration resistant up to 0.7 g
Amplitude 0.075 mm
Acceleration resistant up to 1 g

Electrical supply conditions

Permissible power systems
TT
TN
IT
≤ 2.5 mm² / AWG 14
≥ 4 mm² / AWG 12
Uo = r.m.s. value external conductor to PE
U = r.m.s. value from external conductor to external
conductor
U = r.m.s. value from external conductor to external
UL
conductor
EN 50598-2
EN 60721-3-1
Storage
EN 60721-3-2
Transport
EN 60721-3-3
Operation
Operation at a switching frequency of 2 or 4 kHz: above
+45°C, reduce rated output current by 2.5 %/°C
Operation at a switching frequency of 8 or 16 kHz: above
+40°C reduce rated output current by 2.5 %/°C
Reduce rated output current by 5 %/1000 m
EN 61800-5-1
UL 61800-5-1
In original packaging
EN 60721-3-2
up to 45 kW
5 ... 13.2 Hz
Germanischer Lloyd
13.2 ... 100 Hz
up to 11 kW
10 ... 57 Hz
EN 61800-5-1
57 ... 150 Hz
Voltage to earth: max. 300 V
Voltage to earth: max. 300 V
Please employ the measures described for IT systems!
IT systems not relevant for UL-approved systems
Technical data
Standards and operating conditions
Electrical supply conditions
189

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading