Verfügbare Sprachen

Technical data
Standards and operating conditions

Environmental conditions

Motor connection

Requirements for the shielded motor cable
Capacitance per unit length
C-core-core/C-core-shielding < 75/150
pF/m
C-core-core/C-core-shielding < 150/300
pF/m
Electric strength
Uo/U = 0.6/1.0 kV
U ≥ 600 V
Environmental conditions
Energy efficiency
Class IE2
Climate
1K3 (-25 ... +60°C)
2K3 (-25 ... +70°C)
3K3 (-10 ... +55°C)
Site altitude
0 ... 1000 m amsl
1000 ... 4000 m amsl
Pollution
Degree of pollution 2
Vibration resistance
Transport
2M2 (sine, shock)
Operation
Amplitude 1 mm
Acceleration resistant up to 0.7 g
Amplitude 0.075 mm
Acceleration resistant up to 1 g
98
≤ 2.5 mm² / AWG 14
≥ 4 mm² / AWG 12
Uo = r.m.s. value external conductor to PE
U = r.m.s. value from external conductor to external
conductor
U = r.m.s. value from external conductor to external
UL
conductor
EN 50598-2
EN 60721-3-1
Storage
EN 60721-3-2
Transport
EN 60721-3-3
Operation
Operation at a switching frequency of 2 or 4 kHz: above
+45°C: reduce rated output current by 2.5 %/°C (I55AP222B
at 4 kHz + 40°C)
Operation at a switching frequency of 8, 12 or 16 kHz:
above +40°C: reduce rated output current by 2.5 %/°C
Reduce rated output current by 5 %/1000 m
EN 61800-5-1
UL 61800-5-1
In original packaging
EN 60721-3-2
up to 45 kW
Germanischer Lloyd
5 ... 13.2 Hz
13.2 ... 100 Hz
10 ... 57 Hz
EN 61800-5-1
57 ... 150 Hz