Technical data
3-phase mains connection 480 V
Rated data
Inverter
Rated power
Rated power
Mains voltage range
Output voltage
Rated mains current
Without mains choke
With mains choke
Apparent output power
Rated output current
2 kHz
4 kHz
8 kHz
16 kHz
Power loss
2 kHz
4 kHz
8 kHz
16 kHz
For controller inhibit
Cyclic mains switching
Max. motor cable length
shielded
Without EMC category
Category C1 (2 kHz, 4 kHz, 8
kHz)
Category C2 (2 kHz, 4 kHz, 8
kHz)
Category C3 (2 kHz, 4 kHz, 8
kHz)
Weight
Weight
206
I55AE315F
I55AE318F
kW
15
hp
20
A
32.3
A
24
kVA
22
A
27
A
27
A
27
A
18
W
340
W
360
W
460
W
469
W
18
m
100
m
-
m
20
m
35
kg
10.3
lb
23
I55AE322F
I55AE330F
18.5
22
25
30
3/PE AC 340 V ... 528 V, 45 Hz ... 65 Hz
3 AC 0-400/480 V
40.3
47.4
30
35.3
27
32
34
40.4
34
40.4
34
40.4
22.6
26.9
420
491
450
520
570
670
581
680
18
18
3 times per minute
100
100
-
-
20
20
35
35
10.3
10.3
23
23
I55AE337F
I55AE345F
30
37
40
50
-
-
45.7
57
41
51
52
65
52
65
52
65
34.6
43.3
639
790
680
840
880
1100
884
1095
25
25
100
100
-
-
20
20
35
35
17.2
17.2
38
38
45
60
-
66.7
60
77
77
77
51.3
920
980
1280
1278
25
100
-
20
35
17.2
38