Herunterladen Inhalt Inhalt Diese Seite drucken

Lenze i550 Montage- Und Einschaltanleitung Seite 203

0.25 kw ... 132 kw 0.5 hp ... 175 hp
Vorschau ausblenden Andere Handbücher für i550:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Inverter
Rated power
Rated power
Mains voltage range
Output voltage
Rated mains current
Without mains choke
With mains choke
Apparent output power
Rated output current
2 kHz
4 kHz
8 kHz
16 kHz
Power loss
2 kHz
4 kHz
8 kHz
16 kHz
For controller inhibit
Cyclic mains switching
Max. motor cable length
shielded
Without EMC category
Category C1 (2 kHz, 4 kHz, 8
kHz)
Category C2 (2 kHz, 4 kHz, 8
kHz)
Category C3 (2 kHz, 4 kHz, 8
kHz)
Weight
Weight
I55AE355F
kW
75
hp
100
A
-
A
119
kVA
89
A
132
A
132
A
-
A
-
W
1358
W
1446
W
-
W
-
W
30
m
200
m
-
m
20
m
100
kg
24
lb
53
3-phase mains connection 400 V "Light Duty"
I55AE375F
I55AE390F
90
125
3/PE AC 340 V ... 528 V, 45 Hz ... 65 Hz
3 AC 0-400/480 V
-
160
121
180
180
-
-
1841
1961
-
-
30
Once per minute
200
-
20
100
24
53
Technical data
Rated data
I55AE411F
110
132
150
175
-
-
200
234
145
171
216
254
216
254
-
-
-
-
2203
2589
2348
2760
-
-
-
-
30
30
200
200
-
-
20
20
100
100
35.6
35.6
78.5
78.5
203