Technical data

3-phase mains connection 230/240 V "Light Duty"

Rated data

3-phase mains connection 230/240 V "Light Duty"
Rated data
The output currents apply to these operating conditions:
• At a switching frequency of 2 kHz or 4 kHz: Ambient temperature above 40 °C with a rated output current
reduced by 2.5 %/°C.
• If the load characteristic "Light Duty" and the switching frequencies 8 kHz or 16 kHz are selected, only the
values of the load characteristic "Heavy Duty" are reached.
Inverter
Rated power
Rated power
Mains voltage range
Output voltage
Rated mains current
Without mains choke
With mains choke
Apparent output power
Rated output current
2 kHz
4 kHz
8 kHz
16 kHz
Power loss
2 kHz
4 kHz
8 kHz
16 kHz
For controller inhibit
Cyclic mains switching
Max. motor cable length
shielded
Without EMC category
Category C1 (2 kHz, 4 kHz, 8
kHz)
Category C2 (2 kHz, 4 kHz, 8
kHz)
Category C3 (2 kHz, 4 kHz, 8
kHz)
Weight
Weight
196
I55AE240C
kW
hp
A
A
kVA
A
A
A
A
W
W
W
W
W
m
m
m
m
kg
lb
5.5
7.5
3/PE AC 170 V ... 264 V, 45 Hz ... 65 Hz
3 AC 0-230/240 V
25.8
18.9
8
20.6
20.6
-
-
124
131
-
-
6
3 times per minute
50
-
-
-
2.1
4.6
I55AE255C
7.5
10
-
24.2
10.5
27.6
27.6
-
-
190
200
-
-
6
50
-
-
-
2.1
4.6