Electrical installation
Networks

PROFIBUS

PROFIBUS
The network must be terminated with a resistor at the physically first and last node.
Activate the bus terminating resistor at these nodes in the bus connection plug.
Typical topologies
M
Master
S
Slave
Sub D socket 9-pin - X226
View
5
1
5
1
9
6
9
6
Basic network settings
Use the DIP switch to set the station address.
The baud rate is detected automatically.
64
32
OFF
OFF
Station address - example:
OFF
OFF
Station address = 16 + 4 + 2 + 1 = 23
Do not set station address = 126 and station address = 127. These station addresses are invalid.
Bold print = default setting
178
M
R
S11
S12
1
Pin
Assignment
1
Shield
2
n.c.
3
RxD/TxD-P
4
RTS
5
M5V2
6
P5V2
7
n.c.
8
RxD/TxD-N
9
n.c.
64
PROFIBUS
PROFIBUS station address
16
OFF
Value from parameter
ON
Line with repeater
R
X1
R
R
S1n
S21
X
Repeater
R
Activated bus terminating resistor
Description
Additional shield connection
Data line-B (received data/transmitted data +)
Request To Send (received data/transmitted data, no differential signal)
Reference potential (bus terminating resistor -)
5 V DC / 30 mA (bus terminating resistor +, OLM, OLP)
Data line-A (received data/transmitted data -)
32 16
8
4
2
1
O
N
Address
8
OFF
OFF
OFF
ON
R
S2n
2
4
2
OFF
ON
1
OFF
ON