Pulse inputs and outputs (optional)
By meters with pulse inputs, the
pulse value can be called up in the
display (see the display overview,
level 4). The pulse value of the
outputs is permanently set and
corresponds with the last position of
the associated display value.
Typical connection (*)
U = 3 ... 30 V
Imax = 20 mA*
white
yellow
green
brown
(*) The connection of the external
resistor could be necessary to en-
sure an integrated current limiter.
Example:
Output 1 = energy output
Energy display = XXXXX.XXX
Last position = 0.001 MWh = 1 kWh
Output pulse = 1 kWh
colour
connection
white
I/O 1
yellow
I/O 2
green
I/O 3
brown
GND
Technical data I/O
Load
I/O 1, 2, 3
Cable
Pulse-duty
factor
Cable length
Input
frequency
V Out
Pulse
pulse
GND
signification
In-/Output 1
In-/Output 2
In-/Output 3
common ground
for I/O 1-3
max. 30V DC/20 mA
Open Drain, n-channel
FET
D = 3.8 mm, 4-wire
1:1 (out); 1:5 (in)
1.5 m
max. 1 Hz
M-Bus (optional)
The optional M-Bus interface com-
plies with standard EN 1434-3 and
operates with 2400 baud fixed. The
two conductors can be connected in
any order to the M-Bus network.
A firmly attached cable is included,
external wiring must be done by
oneself.
Technical data M-Bus
Cable length
Cable
colour
connection
brown
M-Bus 1
white
M-Bus 2
Programming of M-Bus address
(optional)
Select of the display „Adr 000" in
■
level 3 (same for the additional
inputs „Adr1" to „Adr3").
Press the button for about 2
■
seconds (until the door symbol
reappears) and then release. The
right digit starts flashing. With
one short push the value of the
digit is incremented.
With each long press, the selected
■
value will be taken over and
change to next digit (as soon as
desired character flashes, release
the button).
If the desired value is reached,
■
you have to press the button
until the number stops flashing
and the return to the menu is
completed. Now the new value is
programmed.
The programming process can be
■
repeated if necessary.
Note: If the editor is not terminated,
maybe changed values are being
saved after the automatic return to
the main display.
1.5 m
D = 3.8 mm, 2-wire
signification
M-Bus-
cable 1
M-Bus-
cable 2
23