36

10.3 LED displays

The following LED displays exist:

1. Module LED

2. LEDs in the Ethernet connection

3. Status LEDs for operating status

4. Status LEDs for digital outputs

5. LED for operating state of CF card (rear of module)
10.3.1Module LED
The module LED (see Fig. 3.1 on Page 12) lights up green when the power
supply of the CX22‐W is present. The module requires approx. 2 minutes after
switch on before the boot process is complete. The start of the boot process is
signaled by beep sounds.
10.3.2LEDs in the Ethernet connection
The left LED (see Fig. 3.1 on Page 12) indicates whether the network connec­
tion is working with 10/100 MBit (LED off) or with 1 GBit (LED green).
The right LED indicates that data is being transmitted by flashing yellow.
10.3.3Status LEDs for operating status
The "RECORDING" LED lights up continuously yellow when measured data
are being recorded. If a start trigger was set, the LED flashes yellow while
waiting for the trigger event.
The "ERROR" LED lights up yellow if there is an error in catman
when the connection to devices at project start cannot be set up or if the DAQ
job cannot be started. The LED flashes if the available free memory drops
below 1 GByte.
All LEDs can also be triggered via Limit values and events in catman
To do this, select Set digital output: CX22 digital output in the dialog Con­
figure limit value and event monitoring and enter the required LED under
Bit/Condition. The corresponding digital output is simultaneously triggered
with LEDs 4 to 6. The LEDs light up when the relevant output is set to HIGH.
10.3.4Status LEDs for digital outputs
The LEDs show the state of the digital outputs 4 to 6. The outputs are
addressed via LEDs 4 to 6 in catman
HBM
QuantumX Data Recorder CX22‐W
®
AP.
®
AP, e. g.
®
AP.
A3169-1.0 en/de