Herunterladen Inhalt Inhalt Diese Seite drucken

Siemens SIMOVERT MASTERDRIVES Betriebsanleitung Seite 195

Vorschau ausblenden Andere Handbücher für SIMOVERT MASTERDRIVES:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

02.2008
X6 – Braking
resistor connection
PE
H
G
CAUTION
X7 – Pre-charging of
capacitor module
CAUTION
DANGER
Siemens AG
6SE7087-6JP60
SIMOVERT MASTERDRIVES
The connection of the external braking resistor is to a terminal block on
the top of the unit on the left next to the mains connection.
Terminal
PE
Protective conductor connection
H
G
Connectable cross-section: 10 mm² (AWG 4), stranded
Viewed from the front, Terminal PE is at the left.
Table 7-12
Braking resistor connection
Length of connecting cable between converter and brake resistor
< 15 m.
The connection for pre-charging the capacitor module is on the top of
the unit.
Terminal
Connectable cross-section: 4 mm² (AWG 10)
Terminal D' is at the front when installed.
Table 7-13
Connection of precharging capacitor module
The connector has to be screwed firmly to the housing (providing
resistance to vibration and protecting against being inadvertently
withdrawn).
♦ During operation, the full DC link voltage is always present at the
terminals for pre-charging the capacitor module.
♦ During pre-charging, the charging current of all connected capacitor
modules flows via the terminals.
♦ For reasons of protection, cables with 4 mm
connection X7!
Operating Instructions
Meaning
Braking resistor connection
Braking resistor connection
Meaning
Pre-charging of capacitor module
Pre-charging of capacitor module
Pre-charging of capacitor module
Pre-charging of capacitor module
Connecting-up
2
Cu should be used at
7-11

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis