Herunterladen Inhalt Inhalt Diese Seite drucken

Electrical Interconnection In Explosion Risk Area - ABB SensyTemp TSP serie Inbetriebnahmeanleitung

Temperaturfühler
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
Electrical connection
4.1.2.1

Electrical interconnection in explosion risk area

Special interconnections are required for use in hazardous areas depending on the safety
requirements.
Intrinsic safety
The feed separator / SPS inputs must have corresponding input protection circuits available in
order to eliminate a hazard (spark formation). An interconnection inspection must be performed.
For proof of the intrinsic safety, the electrical limit values are to be used as the basis for the
prototype test certificates of the apparatuses (devices), including capacitance and inductivity
values of the wires. The proof of the intrinsic safety is given if the following conditions are
fulfilled with comparison of the limit values of the aparatus.
Transmitter
(intrinsically safe apparatus)
Fig. 3
A Transmitter
Note
Observe the "Technical specifications" and "Explosion-protection technical data" chapters (see
data sheet and/or operating instructions).
12 - EN
U
i
I
i
P
i
L
+ L
(cable)
i
c
C
+ C
(cable)
i
c
Field (Ex area)
SensyTemp TSP
Feed separator / SPS input
(related apparatus)
Control room (secure area)
B Feed separator / SPS input with feed
U
o
I
o
P
o
L
o
C
o
CI/TSP-X1

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis