Installation

2.6

Configuration

The configuration of the temperature sensor with transmitter is permitted within the explosion-
protection areas subject to the interconnection certificate both directly in the area requiring
explosion protection via approved handterminals as well as via the interconnection of an Ex-
modem to the circuit outside of the area requiring explosion protection.
2.7

Explosion-protection relevant information

The detailed explosion protection-relevant information is located in the "Explosion protection-
relevant information" chapter in the operating instructions.
3
Installation
3.1

General

Caution – cancellation of the IP protection class!
The IP protection class of the temperature sensor TSP (IP 6x) is cancelled by damages to
components such as e.g. housing, threads, cable glands or seals!
Install connection lines, terminal blocks and connection points properly. Observe the
respective IP protection class and Ex approvals (e.g. EEX d cable glands) when replacing
cable glands.
The temperature sensors (thermocouple, resistance thermometer) must be brought into the
best possible contact with the medium to be measured.
The connection lines must be firmly connected with the connection terminals.
Observe the correct polarity for thermocouples.
Observe the protection type for 2-wire, 3-wire, or 4-wire connection.
When installing in thermowell, observe that the temperature sensor can be moved slightly. If
this is not the case, the inside of the thermowell must be cleaned.
The diameter of the connection lines must be selected according to the cable entry points on
the connection head.
The temperature sensor must be firmly and securely installed according to the application
process.
Observe the specified protection type. (single or double measuing insets 2-wire, 3-wire, or 4-
wire connection)
After clamping the connection lines using a suitable tool (screwdriver, wrench), ensure that
the connection heads are securely closed and sealed. Be sure to observe here that the
sealing rings of the connection head are clean and undamaged.