WARNING
• The appliance shall be stored in a room without continuously operating ignition sources (for exam-
ple: open flames, an operating gas appliance or an operating electric heater).
• Do not pierce or burn.
• The appliance shall be stored so as to prevent mechanical damage from occurring.
• Be aware that the refrigerants may not contain an odour.
• Compliance with national gas regulations shall be observed.
• Keep ventilation openings clear of obstruction.
• A warning that the appliance shall be stored in a well-ventilated area where the room size corre-
sponds to the room area as specified for operation.
• Any person who is involved with working on or breaking into a refrigerant circuit should hold a
current valid certificate from an industry-accredited assessment authority, which authorises their
competence to handle refrigerants safely in accordance with an industry recognised assessment
specification.
• Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance
and repair requiring the assistance of other skilled personnel shall be carried out under the supervi-
sion of the person competent in the use of flammable refrigerants.
• Appliance shall be stored in a well-ventilated area where the room size corresponds to the room
area as specified for operation.
• Appliance shall be stored in a room without continuously operating open flames (for example an
operating gas appliance) and ignition sources (for example an operating electric heater).
• Appliance shall be installed, operated and stored in a room with a floor area larger than X m2, instal-
lation of pipe-work shall be kept to a minimum X m2(Please see the following form).
The appliance shall not be installed in an unventilated space, if that space is smaller than X m2
(Please see the following form ).Spaces where refrigerant pipes shall be compliance with national
gas regulations.
Model (Btu/h)
<30000
<30000
30000-48000
30000-48000
>48000
>48000
◄ Page 6 ►
Amount of refrigerant
to be charged (kg)
<2.048
<2.048
2.048-3.0
2.048-3.0
>3.0
>3.0
maximum installation
height (m)
1.8m
0.6m
1.8m
0.6m
1.8m
0.6m
Minimum room area
(m
)
2
4
35
8
80
9
80