Battery change
Preparation:
1. Connect position indicator to supply voltage.
2. Place the replacement battery unit ready (see chapter 6.1).
3. Place a Phillips screwdriver ready (e. g. PH 0x60).
Deinstallation (see
1. The battery compartment is situated on the left side of the device
2. Unscrew 3 fastening screws
3. Take out the battery unit
Installation (see
1. Insert new battery unit
2. Check the correct position of the O ring
Fig. 9: Battery change

6.4 Faults after battery change

Data loss
NOTICE
Battery symbol on display is glowing in spite of new battery.
` Await updating. The battery's state-of-charge display is updated at
` Insufficient contact, repeat chapter 6.3.
` Disconnect the position indicator from the supply voltage. With
AP05 · Date 25.09.2018 · Art. No. 88847 · Mod. status 316/18
Fig.
(connections below).
battery).
Fig.
9):
tery unit,
the O-ring must lie all round the battery housing.
2
1
2
3
intervals of <10 min.
repeated applying of supply voltage, the battery display will be initial-
ized and updated. Execute calibration travel according to User man-
ual.
9):
.
1
(refer to chapter
2
. Take care that it can be inserted easily.
2
3
4
English
7
for disposal of the old
. When mounting the bat-
Screw
1
Battery unit
2
O ring
3
Housing
4