Installation
Connection diagram
Faulty or missing termination
CAUTION
Faulty or missing termination or level specification results in communica-
tion errors and can destroy the drive's electronic system.
` Make sure that termination is correct and test it.
Connection diagram and level specification RS485
If termination and level specification do not occur in the bus master, they
must be carried out externally.
Fig. 4: Connection diagram and level specification RS485
Data transfer RS485 interface
RS485 baud rate
115.2 kbit/s
57.6 kbit/s
19.2 kbit/s
Connection diagram CAN
A terminating resistor (120 Ohm) is required for the fieldbus function,
which must be included at the last bus subscriber between CANH and
CANL.
AP05 · Date 25.09.2018 · Art. No. 88847 · Mod. status 316/18
+5 V
470 R
RS485+
120 R
RS485-
470 R
SGND
0 V
24 V
Node 1
max. bus network length
200 m
400 m
1200 m
DÜA
120 R
DÜB
0 V
24 V
Node n