Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Specifications; General Detector Specifications - Honeywell UniVario FMX5000 UV.ESSER Bedienungs- Und Installationsanleitung

Uv-flammenmelder
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

UV-Flame detector UniVario FMX5000 UV.ESSER

11 Technical Specifications

Operating voltage
Quiescent current incl. EOL-UV
Alarm current incl. EOL-UV
Application temperature
Storage temperature
Rel. humidity
Protection class
Housing
Colour
Weight
Dimensions (W x H x D)
Specification
VdS certification
Declaration of performance

11.1 General Detector Specifications

Monitoring height
Monitoring area
Wall or corner installation (VdS)
Max. usage elevation above sea level
Atmospheric pressure
Viewing angle
Measurement principle
Spectral detectivity
Trigger thresholds
Detection criterion
Number of detectors per detector zone :
Fault indicator, yellow
Connection terminals
Loop length transponder ↔ UniVario
Cable screw connection
CE directives
The flame detector requires approx. 6 seconds to return to operational readiness
after a reset.
42
:
9 V DC
:
approx. 1,36 mA @ 9 V DC
:
approx. 19,6 mA @ 9 V DC
:
-20 °C ... +80 °C
:
-40 °C ... +85 °C
:
≤ 95 % rel. humidity (non-condensing)
:
IP 67
:
die cast aluminium
:
red (similar to RAL 3000)
:
approx. 945 g (incl. base and bracket)
:
130 x 140 x 92 (mm)
:
EN 54-10 : 2002 / A1 : 2005
:
G 208131
:
DoP-20567130701
:
max. 45 m
:
max. 676 m
2
:
cuboidal room volumes
with an edge length of max. 26 m
:
approx. 3,500 m
:
66 kPa to 106.7 kPa
:
90°
:
Sensor for UV-C radiation from a flame
:
185 nm to 260 nm
in accordance with EN 54 – 10, Class 1
:
UV intensity change
1
:
approx. 10,3 mA @ 9 V DC
:
0.5 mm ... 2.5 mm
:
max. 100 m
:
M 16 x 1.5 metal screws (2 pcs.)
:
2004/108/EC (EMC)
89/106/EEC (construction products directives)
2
FB 798658 / 06.15

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading