7.4

Detection sensitivity and distance

The sensitivity of the flame detectors to different combustible materials was measured during
fire testing. The following table indicates the most suitable flame detector depending on the
combustible material contained in the object in question (flammable liquids or solid materials).
The table gives the detection sensitivity (detection distance) as a percentage in relation to an n-
heptane standard fire (0.1 m² fire pit, 0.5 liter).
Percentage Sensitivity for FMX5000 UV.ESSER
Flammable liquid
AvGas 100
Fuel oil / diesel
Jet-A1
JP 8
n-Heptane
Cruid oil Northsee BP
Ethyl alcohol (Spiritus)
Fuel (Super)
Ethane
Methane
Propane
Hydrogen
Sensitivity to combustable material for FMX5000 UV.ESSER
Flammable liquid
Cotton loose
100 g
Cotton loose
500 g
Beech wood
70 wood slats 1 x 2 x 25 cm³ (EN54-9)
Magnesium dry
100 g
Magnesium with cutting oil
100 g
Sulfur powder
300 g
on cook plate liquified
0,25 x 0,25 m² pan
30
(0,1 m², 0,5 liter)
(0,1 m², 0,5 liter)
(0,1 m², 0,5 liter)
(0,1 m², 0,5 liter)
(0,1 m², 0,5 liter)
(0,2 m², 0,5 liter)
(0,25 m², 1,5 liter)
(0,1 m², 0,5 liter)
(28 l/min, 4,0 mm nozzle, 0,5 m flame)
(48 l/min, 6,0 mm nozzle, 0,5 m flame)
(20 l/min, 2,5 mm nozzle, 0,5 m flame)
(20 l/min, 2,5 mm nozzle, 0,2 m flame)
10 m
15 m
30 m
20 m
20 m
10 m
100%
55%
80%
80%
100%
80%
80%
80%
100%
90%
90%
30%