UV-Flame detector UniVario FMX5000 UV.ESSER
9
Installation
•
The connection must be performed with great care.
•
The cable insulation must extend up to the terminal connection. Take care not to damage
the wires when stripping insulation.
•
It must be ensured through appropriate selection of the cable types as well as the method
of laying the cables that the maximum permissible temperatures are not exceeded.
•
The maximum line lengths and maximum voltage attenuation must be observed.
Connection cable
Use communications cable I-Y (St) Y n x 2 x 0.8 mm with special labelling or fire
alarm cable!
The signal wires are protected against interference through connection of the cable
shielding.
9.1
Configuration
The detector is configured using the DIL switch.
Fig. 5: Location and factory setting = OFF
Check DIL switch settings before commissioning!
34
DIL switch
Function
OFF
1
Reed contact active
2
No function
3
UV sensor test on
4
No function
5
No function
6
No function
7
No function
8
No function
FB 798658 / 06.15