Herunterladen Inhalt Inhalt Diese Seite drucken

Status Indicators - Honeywell UniVario FMX5000 UV.ESSER Bedienungs- Und Installationsanleitung

Uv-flammenmelder
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

7.1

Status Indicators

The flame detector has one red and one two-colour, green/yellow status indicator.
Fig. 1: Status indicators
Operating (LED
This LED indicates two states:
In operational condition, the green LED blinks at 10-second intervals.
Fault (LED
yellow)
The green LED is not blinking.
The yellow fault LED lights up when a detector zone is detected (error).
The current to this detector zone increases by approx. 9 mA.
The condition is not stored and the indicator remains active only for as long as the error is
present.
Exception: If the detector was operated for an extended period outside of the permissible
temperature range or faulty functioning of the DIL switch is detected, a constant error is
indicated.
Alarm (LED
red)
The red LED is lit.
The current to this detector zone (alarm) increases by approx. 18,3 mA.
Optionally, a parallel detector indicator (e.g. Part No. 801824) can be connected via a relay
of the esserbus
®
FB 798658 / 06.15
UV-Flame detector UniVario FMX5000 UV.ESSER
2
LED
LED
1
green)
transponder (Part No. 808623.10).
27