Connection - Honeywell UniVario FMX5000 UV.ESSER Bedienungs- Und Installationsanleitung

Uv-flammenmelder
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

9.2

Connection

The esserbus
transponder for UniVario (Art.-Nr. 808623.10) and the voltage converter
®
(Part No. 781337) are required for connecting the flame detector to the FACP. Only a single
flame detector may be connected at each detector zone input.
System limits
max. 100 esserbus
max. 31 esserbus
max. 127 zones per loop
max. 1 UniVario detector per zone input on the transponder
max. 2 UniVario detectors per esserbus
BM Z / FA CP
Netzteil / Power supply
GND
+U
12V DC /
bext
Ringmodul /
Loop module
A+
A-
B+
B-
Fig. 1: Connection example
Observe max. loop length power supply ↔ esserbus
Connect an end-of-line element (EOL-UV) (Part No. 808626.10) to each
flame detector and a 4.7 kΩ end-of-line resistor to any unused zone inputs.
Four end-of-line resistors and two end-of-line elements (EOL-UV) are included
in the esserbus
For additional information refer to esserbus
FB 798658 / 06.15
UV-Flame detector UniVario FMX5000 UV.ESSER
®
transponders per fire alarm control panel
®
transponders per loop
Spannungskonverter
DC / DC converter
24 V DC
12 V
®
transponder accessory kit.
®
transponder
X 1
1 2
1 1
1 0
9
8
7
6
5
4
3
2
F 2
F 1
K 2
K 1
8 0 8 6 2 3 .1 0
V 10
V 9
1 3
1 4
1 5
1 6
1 7
1 8
1 9
2 0
2 1
2 2
2 3
X 2
4,7K 4,7K 4,7K
max. 100 m
®
transponder documentation.
1
2 4
UniVario
+UL
+UL
-UL
EOL-UV
-UL
+UF
+UF
Ext
T/R
nicht beschalten
do not connect
®
transponder!
35