Inverter Size
Housing size
Phases
Output nominal power
Max. rated motor power
Output nominal current
1)
Max. short time current
OC-tripping current
Nominal input current
Max. permissible mains fuse (inert)
Rated switching frequency
Max. switching frequency
Power loss at nominal operating
2)
Stall current at 4kHz
2)
Stall current at 8kHz
2)
Stall current at 16kHz
Max. heat sink temperature TOH
3)
Motor line cross section
4)
Min. braking resistor
4)
Typ. braking resistor
Max. braking current
Overload curve (page appendex)
Tightening torque for terminals
5)
Mains voltage
Mains frequency
Output voltage
Output frequency
Max. shielded motor line length
Storage temperature
Operating temperature
Model / protective system (EN 60529)
Environment (IEC 664-1)
EMC tested according to
Vibration/Jolt according to
Climatic category (EN 60721-3-3)
The technical data is for 2/4-pole standard motors. With other pole numbers the inverter must be dimensioned onto the
motor rated current. Contact KEB for special or medium frequency motors.
Site altitude max. 2000 m. With site altitudes over 1000 m a power reduction of 1% per 100m
must be taken into consideration.
An input choke is necessary from size 23.
20
21
H
R
R
3
3
[kVA]
52
62
[kW]
37
45
[A]
75
90
[A]
112
135
[A]
135
162
[A]
83
100
[A]
100
160
[kHz]
2
8
4
[kHz]
8
16
16
[W]
900
1000 1100 1200 1500 1300 1900 1700 2000 2400
[A] 67,5
75
90
[A] 52,5
75
63
[A]
-
34
45
[°C]
[mm²]
35
50
[Ohm]
9
9
[Ohm]
12
10
[A]
88
88
[Nm]
4
6
6
[V]
305...500 ±0 (400 V Nominal voltage)
[Hz]
[V]
[Hz]
[m]
-10...45 °C (14...113 °F)
Germanischer Lloyd; EN 50155
22
23
R
R
U
3
3
80
104
55
75
115
150
172
225
207
270
127
165
160
200
8
4
8
2
8
16
12
8
115 115 127,5 150 144
90
80
115
90
150 108
54
46
51
-
-
90
50
95
8
6
5
8,6
6,7
100
133 160
1
6
15
50 / 60 +/- 2
3 x 0...U Mains
see Control board
50
-25...70 °C (-13...158 °F)
IP20
Pollution degree 2
EN 61800-3
3K3
24
R
U
3
125
90
180
270
324
198
315
2
4
8
8
180
180
-
-
95
5
5
200
15
-10...40 °C
11