1.4
DC Supply
The DC input current of the inverter is basically determined by the used motor.
The data can be taken from the motor name plate.
400V Class:
√3 x rated motor voltage x rated motor current x motor cos ϕ
The DC input peak current is determined by the operating range.
•
if you accelerate on the hardware current limit, the short-time current limit of
the inverter must be used in the formula above (instead of the rated motor
current.
•
if the motor in normal operation is never stressed with rated torque, it can be
calculated with the real motor current.
•
a good practice value corresponds approx. to 1,5-times of the rated motor
current (from 90kW 1,25-times)
540V