Service Class 3
Class 3 comprises status codes that may appear during feed-in operation and that do not
cause a permanent interruption of the operation of feeding power into the grid.
After automatic disconnection from the grid and waiting for its conditions to return to those
stipulated, your inverter will try to resume feed-in operation.
Code
Description
301
Current peak found on grid
302
Current peak found on PV
generator
303
Heat sink temperature too
high
306
POWER LOW
78
Behavior
No error - AFCI triggered. Error
visible for 4 seconds, then 241
AFCI triggered. To continue
the process, press Enter 2x
(first 242, then process is con-
tinued)
Behavior
1. Voltage drop in public grid
2. Grid impedance outside of
permissible values
3. Bad contact: wall bracket <-
-> inverter
4. Measurement error on pow-
er module/filter PC board
5. Incorrect capacity on device
1. Bad contact: wall bracket <-
-> inverter
2. Voltage drop in public grid
3. Measurement error on pow-
er module
1. Ventilation opening blocked
2. Ambient temperature too
high
3. Internal or external fans not
connected
4. Internal or external fans
faulty
5. Bad contact: power module
<--> heat sink
6. Measurement error on pow-
er module
7. Ventilator power on Recerbo
faulty
1. DC power too low for infeed
2. Measurement error on pow-
er module
Remedy
Check PV generator
Remedy
1. Automatic correction
2. Contact energy provider
3. Check fixing screws in DAT-
COM area
4. Replace inverter/filter PC
board
5. Replace inverter
1. Check fixing screws in DAT-
COM area
2. Automatic correction
3. Replace power module
1. Clean openings
2. Change setup location
3. Connect fan cable
4. Replacing fans
5. Check phase change paste
6. Replace power module
7. Replace Recerbo
1. Wait for more radiation in-
tensity or check solar modules
2. Replace power module