Replacing the 8k2
Removing the external fan:
external fan
(3)
(2)
(1)
(2)
(1)
(3)
(6)
(4)
NOTE! Carefully turn the inverter
round.
Plug the fan cable (1) into the SymoFIL
6
and place it in the cable guide (2)
Close the inverter and place it in the
7
wall bracket (see "Opening and closing
the device")
After switching on the inverter, carry out a
fan test via the display (see operating inst-
ructions)
WARNING! Observe the safety
rules (see the beginning of the
"Safety" section)
Take the inverter out of the wall bra-
1
cket and open it (see "Opening and
closing the device")
Disconnect both fan cables (1) from
2
the SymoFIL and remove the lower
one from the cable guide (2)
NOTE! Turn the inverter carefully
so that the back of the inverter is
accessible.
Undo the two 5x14 TX25 screws (3)
3
Undo the locking devices (6) on both
4
sides of the air guide
Pull out the sealing plugs (4) on both si-
5
des
Carefully remove the air guide, making
6
sure that the fan cables are threaded
out