Attach the power stage set cover to the
2
(5)
fasteners (5) at the top
While keeping the power stage set co-
3
ver at an angle, pull it downwards and
pivot it onto the base shell
CAUTION! It is essential to follow
this procedure to ensure that the
sealing foam is in the correct posi-
tion to form a seal
Fit the power stage set cover with four
4
5x18 TX25 screws and seal rings (4)
(4)
[2.5 Nm]
NOTE! If the screws no longer fit
tightly, they must be replaced with
new 5x25 TX25 screws
[42,0401,4231]
(4)
NOTE! To avoid damaging the
base shell, do not angle the invert-
er by more than 11°.
Attach the inverter at the top and allow
5
(3)
it to engage in the wall bracket
Fit the two 5x25 TX25 screws (3) to
6
hold the inverter securely in the wall
bracket
[2.5 Nm]
If applicable, connect all plug connec-
7
tions
Fit the Datcom cover with two 5x25
8
TX25 screws (2)
[2.5 Nm]
Set the DC disconnector (1) to the I po-
9
sition
(2)
107