Herunterladen Inhalt Inhalt Diese Seite drucken

Fronius Symo 3.0-3-S Serviceanleitung Seite 89

Netzgekoppelter wechselrichter
Vorschau ausblenden Andere Handbücher für Symo 3.0-3-S:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Code
Description
451
Flash of the guard defective
452
Communication between
filter & power stage set
faulty
453
Processor guard detected a
faulty grid voltage
454
Processor guard detected a
faulty grid frequency
456
Error in the Anti Islanding
monitoring detected
457
Grid relais do not release
458
RCMU selftest failed
459
Faulty isolation measure-
ment
460
Reference voltage outside
permitted limits
461
Defective data memory
462
Failure on the DC injection
monitoring detected
Behaviour
1. Grid problem
2. Defective AC guard on filter
board
3. Defective AC guard on pow-
er stage set
1. Communication problem
caused by temporary environ-
mental disturbances (grid,
EMC, ...)
2. Ribbon cable between filter
board and power stage set de-
fective
3. Defective AC guard on filter
board
4. Defective AC guard on pow-
er stage set
1. Measuring error
2. Grid problem
3. Defective AC guard on filter
board
4. Defective AC guard on pow-
er stage set
1. Measuring error
2. Grid problem
3. Defective AC guard on filter
board
4. Defective AC guard on pow-
er stage set
1. Occurs once
2. Software problem
3. Measuring on filter board
4. Measuring circuit for Anti Is-
landing defective
1. Occurs once
2. Grid test time is too low
3. Relay got stuck
1. RCMU measurement defect
1. Occurs once
2. Isolation measuring defec-
tive
1. Occurs once
2. Measuring circuit on power
stage set defective
1. Defective power stage set
1. Occurs once
2. DC injection monitoring de-
fective
Remedy
1. Automatically corrected
2. Change filter board
3. Change AC board
1. Automatically corrected
2. Change ribbon cable
3. Change filter board
4. Change AC board
1. Software update
2. Automatically corrected
3. Change filter board
4. Change AC board
1. Software update
2. Automatically corrected
3. Change filter board
4. Change AC board
1. Restart inverter
2. Software update
3. Change filter board
4. Change AC board
1. Restart inverter
2. Change settings
3. Change AC board
1. Change filter board
1. Restart inverter
2. Change DC board. After-
wards if necessary AC board
1. Restart inverter
2. Change AC board
1. Change DC board. After-
wards if necessary AC board
1. Restart inverter
2. Change inverter
89

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading