Fronius Symo 3.0-3-S Serviceanleitung Seite 92

Netzgekoppelter wechselrichter
Vorschau ausblenden Andere Handbücher für Symo 3.0-3-S:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Code
Description
523
DC LOW Ch2
558
Country setup not support-
ed by power stage set
559
Feature nor supported by
Recerbo
560
Power reduction because
of over frequency
565
AFCI SD card failure
566
AFCI deactivated
567
GVDPR active
601
Internal communication
fault
602
Auto test Italy failed
603
Temperature sensor in μC
defect (Ch3 AC Temp)
604
Temperature sensor in DC
module 2 defect (Ch4 DC2)
607
RCMU continous fault oc-
cured more than 4 times in
24 hours
92
Behaviour
1. DC main switch open
2. PV generator not connected
3. DC voltage too low for feed-
ing in
4. Reversal voltage of PV gen-
erator
5. DC operating mode: fix volt-
age and wrong voltage
6. Measuring error on the pow-
er stage set
1. Old software
2. Old software
3. Incompatible hardware com-
binations
1. Old software
2. Old software
3. Incompatible hardware com-
binations
1. Too high grid frequency
2. Grid disturbances
3. Wrong settings
1. Writing data to SD card
failed
1. No error, AFCI is deactivat-
ed
1. Too high grid voltage
2. Grid disturbances
3. Wrong settings
1. Occurs once
2. Occurs permanently
1. Auto test Italy was started
and not finished or failed
1. Defective temperature sen-
sor μC
2. Defective circuit on the pow-
er stage
1. Defective temperature sen-
sor in DC module 2
2. Defective circuit on the pow-
er stage
1. Grounding problem
Remedy
1. Close DC main switch
2. Connect PV generator
3. Wait for more irradiance or
check modules
4. Change polarity of PV gen-
erator
5. Check MPP settings / volt-
age
6. Change DC board. After-
wards if necessary AC board
1. Software update
2. Reload setup
3. Check hardware compo-
nents
1. Software update
2. Reload setup
3. Check hardware compo-
nents
1. Automatically corrected
2. Software update
3. Check settings
1. Format SD card
1. If AFCI has to be switched
on, use tool
1. Automatically corrected
2. Software update
3. Check settings
1. Restart inverter
2. Change AC board
1. Reload setup
1. Change power stack
2. Change AC board
1. Change DC board
2. Change DC board
1. Automatically corrected after
24 hours
2. Check PV array
3. Check wiring