Fronius Symo 3.0-3-S Serviceanleitung Seite 86

Netzgekoppelter wechselrichter
Vorschau ausblenden Andere Handbücher für Symo 3.0-3-S:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Code
Description
302
Current peak on the PV
generator
303
Too high heat sink temper-
ature
306
POWER LOW
307
DC LOW
308
The intermediate circuit
voltage
309
Too high DC1 voltage
313
Too high DC2 voltage
86
Behaviour
1. Bad contact: wall bracket <-
> inverter
2. Voltage drop in the public
mains
3. Measuring error on the pow-
er stage set
1. Ventilation opening blocked
2. Too high ambient tempera-
ture
3. In- or outside fan cable not
connected
4. In- or outside fan defective
5. Bad contact: wall bracket <-
> heat sink
6. Measuring error on the pow-
er stage set
7. Fan output on Recerbo de-
fective
1. DC power is too low for feed-
ing in
2. Measuring error on the pow-
er stage set
1. DC main switch open
2. PV generator not connected
3. DC voltage too low for feed-
ing in
4. Reversal voltage of PV gen-
erator
5. DC operation mode: fix volt-
age + wrong voltage
6. Measuring error on the pow-
er stage set
1. Voltage drop on AC grid
2. Bad contact: wall bracket <-
> inverter
3. Measuring error on the pow-
er stage set
1. PV generator voltage too
high in MPP1
2. Wrong DC cabling in MPP 1
3. Measuring error on the pow-
er stage set
1. PV generator voltage too
high in MPP 2
2. Wrong DC cabling in MPP 2
3. Measuring error on the pow-
er stage set
Remedy
1. Check AC wall bracket
screws
2. Automatic correction
3. Change DC board. After-
wards if necessary AC board
1. Clean openings
2. Change mounting place
3. Connect fan cable
4. Change fan
5. Check phase change paste
6. Change AC board
7. Change Recerbo
1. Wait for more irradiance or
check PV modules
2. Change DC board. After-
wards if necessary AC board
1. Close DC main switch
2. Connect PV generator
3. Wait for more irradiance or
check PV modules
4. Reverse polarity of PV gen-
erator
5. Check MPP settings / volt-
age
6. Change DC board. After-
wards if necessary AC board
1. Automatic correction
2. Check AC wall bracket
screws
3. Change AC board
1. Check PV configuration
2. Check DC cabling
3. Change DC board. After-
wards if necessary AC board
1. Check PV configuration
2. Check DC cabling
3. Change DC board. After-
wards if necessary AC board