3.7.2
Electrical data
Designation
Rated voltage */**
Rated frequency *
Functional area
Power consumption * A35 / A35
Power consumption * A50 / A35
Nominal current *
Start-up current *
MOP (Maximum Overcurrent Protection)***
MCA (Minimum Circuit Ampacity)***
Internal control fuse for transformer. Category
"Class CC", slow-blow, suitable for transformer
protection.
Tab. 9: Electrical data model DTI / DTS 6201
Designation
Rated voltage */**
Rated frequency *
Functional area
Power consumption * A35 / A35
Power consumption * A50 / A35
Nominal current *
Start-up current *
MOP (Maximum Overcurrent Protection)***
MCA (Minimum Circuit Ampacity)***
Internal control fuse for transformer. Category
"Class CC", slow-blow, suitable for transformer
protection.
Tab. 10: Electrical data model DTI / DTS 6301
*
Data on the type plate.
**
In case the rated voltage changes, adapt the upstream fuse, see "Adapting the unit to the mains voltage", Page 48.
***
Data for UL-approved units on the design of the protection (MOP) and cable cross-sections (MCA).
Operating Manual | Attachment and Installation Cooling Units | Multi Controller (MC) – 400 V, 2~ | 086100116
Unit
50 Hz
V
60 Hz
V
Hz
P
50 Hz
W
el
P
60 Hz
W
el
P
50 Hz
W
el
P
60 Hz
W
el
I
50 Hz
A
nom
I
60 Hz
A
nom
I
50 Hz
A
Start max
I
60 Hz
A
Start max
A
A
F2, F3
A
Unit
50 Hz
V
60 Hz
V
Hz
P
50 Hz
W
el
P
60 Hz
W
el
P
50 Hz
W
el
P
60 Hz
W
el
I
50 Hz
A
nom
I
60 Hz
A
nom
I
50 Hz
A
Start max
I
60 Hz
A
Start max
A
A
F2, F3
A
Model DTI / DTS 6201
400 V, 2~
460 V, 2~
50/60
DIN IEC 60038
532
653
607
746
2.4
2.5
5.5
5.5
15.0
3.3
4.0
Model DTI / DTS 6301
400 V, 2~
460 V, 2~
50/60
DIN IEC 60038
778
874
865
961
3.7
2.4
12.0
12.0
15.0
3.9
6.25
27/76