Herunterladen Inhalt Inhalt Diese Seite drucken

12�3 Sdos Error Messages; 12�3�1 Cr2050 - IFM Electronic CR2051 Handbuch

Iocontrol
Vorschau ausblenden Andere Handbücher für CR2051:
Inhaltsverzeichnis

Werbung

12.3 SDOs error messages
12.3.1 CR2050
The following messages are created in case of an error:
Index
S-idx
Designation
0x1001
Error register
0x1003
0x00
Predefined error
field
Number of entries
0x01
Error history
0x02
Error history
0x03
Error history
0x04
Error history
0x05
Error history
0x2020
0x00
Input – short to
supply voltage
0x01
Short to supply
voltage IN00���
IN07
0x02
Short to supply
voltage IN08,
IN10, IN12, IN14
Data type
Default
ro
USINT
0
rw
UDINT
0
ro
UDINT
0
ro
UDINT
0
ro
UDINT
0
ro
UDINT
0
ro
UDINT
0
ro
USINT
2
ro
USINT
0
ro
USINT
0
Details
Error register bitcodiert to profil 301
permissible values:
0b0000 0000 = no error
0b0000 0001 = generic error
0b0001 0000 = communication error
0b1000 0000 = manufacturer specific
An error list with 4 entries is supported�
Error occured; coded according to
EMCY list
The last error is indicated in the sub-
index 1
Error occured; coded according to
EMCY list
Error occured; coded according to
EMCY list
Error occured; coded according to
EMCY list
Error occured; coded according to
EMCY list
Largest sub-index supported
0 = normal
channels (bit coded)
1 = short circuit
0b---- ---X = IN00
0b---- --X- = IN01
0b---- -X-- = IN02
0b---- X--- = IN03
0b---X ---- = IN04
0b--X- ---- = IN05
0b-X-- ---- = IN06
0bX--- ---- = IN07
0 = normal
channels (bit coded)
1 = short circuit
0b---- ---X = IN08
0b---- --X- = IN10
0b---- -X-- = IN12
0b---- X--- = IN14
ioControl
UK
121

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Cr2050Cr2052

Inhaltsverzeichnis