Herunterladen Inhalt Inhalt Diese Seite drucken

12�3�2 Cr2051 - IFM Electronic CR2051 Handbuch

Iocontrol
Vorschau ausblenden Andere Handbücher für CR2051:
Inhaltsverzeichnis

Werbung

12.3.2 CR2051
The following messages are created in case of an error:
Index
S-idx
Designation
0x1001
Error register
0x1003
0x00
Predefined error
field
Number of entries
0x01
Error history
0x02
Error history
0x03
Error history
0x04
Error history
0x05
Error history
0x2022
0x00
Output – short
circuit
0x01
Short circuit
OUT00...OUT07
0x02
Short circuit
OUT08...OUT15
Data type
Default
ro
USINT
0
rw
UDINT
0
ro
UDINT
0
ro
UDINT
0
ro
UDINT
0
ro
UDINT
0
ro
UDINT
0
ro
USINT
2
ro
USINT
0
ro
USINT
0
Details
Error register bitcodiert to profil 301
permissible values:
0b0000 0000 = no error
0b0000 0001 = generic error
0b0001 0000 = communication error
0b1000 0000 = manufacturer specific
An error list with 4 entries is supported�
Error occured; coded according to
EMCY list
The last error is indicated in the sub-
index 1
Error occured; coded according to
EMCY list
Error occured; coded according to
EMCY list
Error occured; coded according to
EMCY list
Error occured; coded according to
EMCY list
Largest sub-index supported
0 = normal
channels (bit coded)
1 = short circuit
0b---- ---X = OUT00
0b---- --X- = OUT01
0b---- -X-- = OUT02
0b---- X--- = OUT03
0b---X ---- = OUT04
0b--X- ---- = OUT05
0b-X-- ---- = OUT06
0bX--- ---- = OUT07
0 = normal
channels (bit coded)
1 = short circuit
0b---- ---X = OUT08
0b---- --X- = OUT09
0b---- -X-- = OUT10
0b---- X--- = OUT11
0b---X ---- = OUT12
0b--X- ---- = OUT13
0b-X-- ---- = OUT14
0bX--- ---- = OUT15
ioControl
UK
123

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Cr2050Cr2052

Inhaltsverzeichnis