Product Information / Produktinformation A6630
Sensor Connections & Mounting
1.7.4 Limiting watching and binary outputs
Limit setting
Configurable in property sheets "Output 1"..."Output 6", 6 output channels with Opto decoupled
collector / emitter−outputs .
Output 1 (OUT−1)
Output 2 (OUT−2)
Output 3 (OUT−3)
Output 4 (OUT−4)
Output 5 (OUT−5)
Output 6 (OUT−6)
Maximum value for outputs
Alarm status of the outputs
Alarm delay
1.7.5 Communication interfaces
RS232 Interface
Front socket to connect a laptop for configuration and visualization purposes
Circular connector on the monitor front
RS 485 Interface
d4, z4 bus interface for communication with analysis and diagnosis systems and for configura-
tion purposes.
1.7.6 Power supply
The system supply voltages and thus also the grounds for the signal and supervision inputs /
outputs are galvanically separated from each other.
Supply inputs
Supply input UB+ / UN+
Common ground, 0 V U−
Perm. voltage range
Power consumption
d26 (collector) / d28 (emitter)
b26 (collector) / b28 (emitter)
z26 (collector) / z28 (emitter)
d30 (collector) / d32 (emitter)
b30 (collector) / b32 (emitter)
z30 (collector) / z32 (emitter)
C−E disabled: max. perm. U
C−E conductive: max. perm. I
Conductive in open circuit mode, disabled in
close circuit mode. Software configurable.
configurable on 0 ... 25,5 seconds,
effective on the alarm outputs
Mini−DIN–socket type TM 0508A/6 for
configuration cable (contained in the
operating kit)
two redundant inputs, decoupled via diodes,
for nominal +24 V with common ground
d2 / z2
b2
19...31,2Vdc (IEC 654−2 class DC 4)
CSA: 24Vdc; SELV LPS
max 5W, at 24 V max. 200 mA
Page 20
: 48V
CE
: 100mA
CE

Werbung