Product Information / Produktinformation A6630
Temperature Monitor
1.5
Installation and Mounting
A prepared 3U slot in a 19" rack, or other Intermas−compatible enclosure, is required for
mounting the A6630 monitor. The slot must be fitted with a 48−pin plug connector (DIN 41612,
design F 48 M). The pin assignment is listed in the following table.
2
UN+ (+ 24V)
4
A (RS 485)
6
CH2−C (input)
8
CH2−A (input)
10
CH2−B (input)
12
I3+ (current output 3)
14
CH3−C (input)
16
CH4−A (input)
18
CH4−B (input)
20
22
CH4−D (input)
24
I4+ (current output 4)
26
OUT−1 (collector)
28
OUT−1 (emitter)
30
OUT−4 (collector)
32
OUT−4 (emitter)
Jumper RS 485
RS 485 bus operation requires an electrical terminator on the first and last bus device.
This is done with plug−in jumpers on the controller board. The figure Fig. 1 shows the position
of the jumpers.
Fig. 1:
RS 485 Jumper position
d
U− (0V/Common)
CH1−D (input)
CH2−D (input)
CH4−C (input)
CH3−B (input)
NC
I2+ (current output 2)
OUT−2 (collector)
OUT−2 (emitter)
OUT−5 (collector)
OUT−5 (emitter)
b
UB+ (+24V redundant)
GND
B (RS 485)
CH1−C (input)
CH1−A (input)
GND
CH1−B (input)
GND
CH3−D (input)
GND
CH3−A (input)
I1+ (current output 1)
GND
BIN1 (binary input 1)
GND
BIN2 (binary input 2)
OUT−3 (collector)
OUT−3 (emitter)
OUT−6 (collector)
OUT−6 (emitter)
Page 10
z
2
4
6
8
10
12
GND
14
GND
16
18
20
22
24
26