Product Information / Produktinformation A6630
Sensor Connections & Mounting
Current outputs of characteristical values
Calculation of characteristical values and evaluation depends on the functions defined during
the configuration.
Current output 1
Current output 2
Current output 3
Current output 4
Common GND
Nominal range
Life zero−mode
Accuracy / resolution
Permissible load resistance
1.7.2 Visualization
2 green status LEDs on the monitor front
left LED
right LED
6 yellow LEDs for the indication of limit exceeding
Limiting value exceeded
No limit value exceeding
1.7.3 Binary inputs
Two inputs for blocking the alarm outputs, resetting of the maximum measured temperature and
resetting of latched alarms.
Binary input 1
Binary input 2
Active
not active
Signal level
Input resistance
I1+: z20
I2+: b20
I3+: d12
I4+: d24
e.g. b10, b12, b14, b22, b24
0...20mA, 4...20 mA, 20...0mA or 20...4mA
depending on configuration
in 4...20mA (20...4mA) operation you can specify via
the configuration that the output is set to 0 mA if a
fault is detected.
±1 % of measuring range value /16 Bit
max. 500 Ω
Supply voltage = OK
Supply voltage = not Ok
Monitor status = Ok
Monitor status = not Ok
BIN1+ (input): z22
BIN2+ (input): z24
Input LOW
Input HIGH or open (not connected)
LOW: 0V ... +3V, HIGH: +13V ... +48V
> 10kΩ
Page 19
Steady light
switched off
Steady light
switched off
Steady light
Switched off