Antriebs- und applikationssteuerung

Werbung

Elektrische Installation
6
UL-gerechte Installation
6.4
UL-gerechte Installation
6.4.1
(Field wiring) Power terminals
6.4.2
Short circuit current rating
6.4.3
Branch circuit protection
Model
PHE1.B-A15-...
PHE2.B-A15-...
PHE3.B-B15-...
6.4.4
Motor overload protection
40
Betriebsanleitung – MOVIPRO
HINWEIS
Folgendes Kapitel wird unabhängig von der Sprache dieser Dokumentation aufgrund
von UL-Anforderungen immer in englischer Sprache abgedruckt. Warnungen werden
zusätzlich in französischer Sprache abgedruckt.
Use 75 °C copper wire only.
Suitable for use on a circuit capable of delivering not more than 5000 rms symmetrical
amperes when protected by 25 A, 600 V non-semiconductor fuses or 500 V minimum
25 A maximum inverse time circuit breakers.
Max. voltage is limited to 500 V.
Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes.
WARNING - The opening of the branch-circuit protective device may be an indication
that a fault current has been interrupted. To reduce the risk of fire or electric shock,
current-carrying parts and other components of the controller should be examined and
replaced if damaged. If burnout of the current element of an overload relay occurs, the
complete overload relay must be replaced.
ATTENTION - LE DÉCLENCHEMENT DU DISPOSITIF DE PROTECTION DU CIR-
CUIT DE DÉRIVATION PEUT ÊTRE DÛ À UNE COUPURE QUI RÉSULTE D'UN
COURANT DE DÉFAUT. POUR LIMITER LE RISQUE D'INCENDIE OU DE CHOC
ÉLECTRIQUE, EXAMINER LES PIÈCES PORTEUSES DE COURANT ET LES AU-
TRES ÉLÉMENTS DU CONTRÔLEUR ET LES REMPLACER S'ILS SONT ENDOM-
MAGÉS. EN CAS DE GRILLAGE DE L'ÉLÉMENT TRAVERSÉ PAR LE COURANT
DANS UN RELAIS DE SURCHARGE, LE RELAIS TOUT ENTIER DOIT ÊTRE REM-
PLACÉ.
For maximum branch circuit protection see table below:
Non Semiconductor Fuses (currents are
maximum values)
25 A/600 V
The devices are provided with load and speed-sensitive overload protection and ther-
mal memory retention upon shutdown or power loss.
®
PHE..B-A15-.1X0..B-00
SCCR: 5 kA/500 V
When protected by:
Inverse-Time Circuit Breaker (currents
are maximum values)
25 A/500 V