Troubleshooting and diagnosis options
Continuation
Error code
0x00000040
0x00000080
0x00000400
0x00000100
0x00000800
0x00000200
0x00010000
Status value
0x00000000
0x00000001
0x00000002
0x00000004
0x00000008
0x00000010
0x00000020
0x00000040
0x00000080
0x00000100
0x00000200
 TR-Electronic GmbH 2007, All Rights Reserved
Page 128 of 131
Meaning
IO-CR error
Parameter:
Length error
Projected DAP:
not supported
Parameter value:
Cannot be stored
Parameter value:
Transmission error
Parameterization:
faulty
Preset value:
Cannot be stored
Meaning
Start value
Measuring system: initialized
CPLD: initialized
PROFINET stack: initialized
Controller: Connect Request transmitted
Controller: Application Relation established
Measuring system: Parameterization executed
Controller: Param End transmitted
Controller: Application Ready received
Sub-module: status set
Controller: communication to the device is running
TR-ECE-BA-DGB-0063 v15
Remedy
- The established
communication relation (RT,
IRT) is not supported from the
measuring system and must
be adjusted corresponding to
the supported Conformance
Class.
- Check projected DAP.
Parameter or DAP is not
supported from the measuring
system.
- Is the correct GSDML file
used?
- Check parameter limit values.
- Execute once more.
- Switch supply voltage off and
then on again. If this measure
is unsuccessful, the measur-
ing system must be replaced.
- Repeat parameter setting.
- Switch supply voltage off and
then on again. If this measure
is unsuccessful, the
measuring system must be
replaced.
- The transmitted preset value
must be within the pro-
grammed measuring range in
steps –1.
Printed in the Federal Republic of Germany
04/25/2022