Parameterization and configuration
6.6 Description of the operating parameters
6.6.1 Rotational direction
Selection
clockwise
counter clockwise
6.6.2 Code SSI-interface
Selection
binary code
gray code
6.6.3 Scaling parameters, C__65_-EPN
The scaling parameters can be used to change the physical resolution of the
measuring system. The position value output is binary decoded and is calculated with
a zero point correction and the count direction set. The measuring system does not
support decimal numbers in this configuration. For the parameters Resolution and
Revolutions only integers can be entered.
 TR-Electronic GmbH 2007, All Rights Reserved
Page 112 of 131
Description
Measuring system position increasing clockwise
(view onto the shaft)
Measuring system position decreasing clockwise
(view onto the shaft)
Description
SSI output code = binary
SSI output code = gray
Danger of personal injury and damage to property exists if the measuring
system is restarted after positioning in the de-energized state by shifting
of the zero point!
If the number of revolutions is not an exponent of 2 or is >4096, it can occur, if
more than 512 revolutions are made in the de-energized state, that the zero
point of the multi-turn measuring system is lost!
Ensure that the quotient of Revolutions Numerator / Revolutions
Denominator for a multi-turn measuring system is an exponent of 2
0
1
of the group 2
, 2
, 2
or
 Ensure that every positioning in the de-energized state for a multi-turn
measuring system is within 512 revolutions.
TR-ECE-BA-DGB-0063 v15
2
12
...2
(1, 2, 4...4096).