Herunterladen Inhalt Inhalt Diese Seite drucken

Hisense Hi-Therma-Serie Bedienungsanleitung Seite 27

Vorschau ausblenden Andere Handbücher für Hi-Therma-Serie:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 185
SPACE HEATING/COOLING AND DHW
Specifications for pressure relief valve (6) (Factory supplied):
Relief Pressure: 0.7± 0.05 MPa
Water flow rate:
Pressure difference
0.05
MPa
Water flow rate
7.2
L/min.
Instructions for pressure relief valve (6) installation:
Make sure that the drainage outlet of the pressure relief
valve is downward for complete drainage.
The drain pipe should always be open to the atmosphere, free of
frost and in continuous slope to the down side in case that water
leakage exists.
The pressure relief valve is to be operated regularly to remove lime
deposits and to verify that it is not blocked;
DHW tank supplies hot water from tap water. Domestic hot
water is only used when tap water is connected.
For safety, do not add ethylene glycol into water circulation. If
added, water will be contaminated when heat exchanger coil
leaks.
When water hardness is more than 250-300 ppm, recommend
using softened water to reduce DHW tank scale.
Immediately flush DHW tank with fresh water after installation.
Flush once every day in first five days of installation.
Try to avoid long runs of water piping between the tank and the
DHW installation in order to decrease possible temperature
losses.
lf the domestic cold water entry pressure is higher than the
DHW tank's design pressure, a pressure reducer must be
fitted.
After used for a while (depend on local water quality and use
frequency), clean DHW tank and remove scales.
a.
Power off and close water inlet valve.
b.
Open water outlet valve and drainage valve to empty
DHW tank.
0.10
0.30
10.0
19.8
When scales are removed, temperature in DHW tank
may be a little high, it should prevent burns or drainage
equipment damaged.
c.
Close drainage valve after cleaning several minutes with
water inlet valve opened. Ensure effluent water is closed
after DHW tank is full of water. Power on and get back to
work.
Always check DHW tank and its surroundings has accumulated
water or not. In case of leaking, contact local dealer.
(2) Elements required for the DHW recirculation circuit
5
4
Nature
No.
1
DHW inlet(Cold water)
Piping connections
2
DHW outlet (Hot water)
3
Water check valve
Field supplied
4
DHW pump
5
Shut-off valve
● A DHW pump (field supplied): This DHW pump (4) will
help to correctly recirculate the hot water to the DHW
inlet. The optional output function of DHW pump (code
13) can be set to drive relay of a DHW pump in case of
DHW pump is available, referring to 10.5.
● A Water check valve (field supplied):
This accessory (3) is connected after the DHW pump (4)
in order to ensure the non-return of water.
● Two Shut-off valves (field supplied) (5):
One before the DHW pump (4) and other after the water
check valve accessory (3).
The DHW tank is equipped with a safety thermostat and
operating temperature of the safety thermostat will be
affected by the altitude (atmospheric pressure). Make sure
max. DHW temperature NOT higher than the following value.
Altitude
Atmospheric pressure
(m)
(mmHg)
4000
424
5000
340
6000
256
16
3
5
2
1
Part name
Max. DHW temperature
°C
(
)
75
70
63

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis