Lock-in device on handwheel with adjustable version
TROUBLESHOOTING
Fault cause
Gas smell
Leaking LPG is extremely
flammable.
Can cause explosions.
Abnormal flame pattern of
adjustable and non-adjustable
pressure regulator
Abnormal flame pattern
of adjustable pressure
regulator
No gas flow
Safety overpressure shut-off
valve (OPSO) has responded:
Visual indicator RED
OPSO cannot be unlocked
Artikel-Nr. 05 239 50 l
1. Loosen handwheel:
2. Adjust the outlet pressure:
seen on the pressure gauge (option).
3. Lock the handwheel:
the housing of the handwheel with an
Action
Close the gas supply.
Do not use any electric switches.
Do not use a phone in the building.
Ventilate rooms well.
Shut down the LPG system.
Contact a specialised company.
Compare the nominal outlet pressure of the pressure
regulator with the nominal inlet pressure of the connected
consuming device:
if they do not correspond, replace the pressure regulator
or the gas appliance.
Measure the outlet pressure of the pressure regulator;
outlet pressure is not within the specified limits:
check the system configuration,
readjust the outlet pressure.
Gas feed is closed:
open the gas cylinder valve or the shut-off fittings.
Safety overpressure shut-off valve (OPSO) is closed:
carry out the steps described in "Restarting the safety
overpressure shut-off valve (OPSO)".
Filter sieve in the input connection is dirty:
send the pressure regulator to the manufacturer to be
checked
OPSO is closed:
causes (remedy of defects):
pressure increase, pressure regulator fault, etc.,
open OPSO manually by following the steps in
"Restarting the safety overpressure shut-off valve (OPSO)".
Outlet pressure is permanently too high:
pressure regulator is damaged, replace.
unscrew the set screw
handwheel slightly using an Allen key.
Adjust the required outlet pressure by
turning the handwheel (turning clock-
wise = increases the outlet pressure).
The outlet pressure can be
tighten the set screw in the grooveon
Allen key.
of the
27 / 120