Example of applications: Tank system
according to A3 B3/4 - 1st stage regulator
1st stage for outdoor installations "f", for
connecting directly to the gas tank
Risk of asphyxiation from gas leaks in enclosed spaces.
High concentrations of gas can cause difficulty in breathing and lead to unconsciousness.
A discharge line must be connected from the breather on the product
outdoors.
For this purpose, install the venting and ventilation set (see LIST OF ACCESSORIES).
Screw connections
If connections leak, there is a danger of explosion, fire or suffocation!
Gas may escape if the product is turned.
Do not turn the product after it has been installed and the connections have been
tightened.
Tighten connections only when they are not pressurised.
Risk of injuries due to blown-out metal chips!
Metal chips may cause eye injuries.
Wear safety goggles!
Assembly notes
Malfunctions caused by residues! Proper functioning is not guaranteed.
• Visually check that there are no metal chips or other residues in the connections!
• It is important that metal chips or other residues are blown out!
Install with suitable tools, if required.
Regarding screw connections, use a second spanner to brace against the connection nozzle.
Do not use unsuitable tools, such as pliers.
Install the pressure regulator so that it is not under tension.
Use the regulator support.
Product damaged through incorrect installation direction
Proper functioning is not guaranteed.
• Observe the installation direction (marked on the product with an arrow
To install the connections, see CONNECTIONS in the assembly manual.
If compression/separation connectors are used in the building, a 1st stage regulator with
maximum 1 bar shut-off pressure of the safety overpressure shut-off valve (OPSO) must be
used.
During installation make sure that the withdrawal valve and the piping are aligned. Do not
install the tank regulator under tension. We recommend the "regulator support for
CE tanks", Part no. 02 510 40.
Artikel-Nr. 05 239 50 l
Example of applications: Tank system
according to A4 B3/4-t - 1st stage regulator
1st stage for indoor installations "t", for
connecting directly to the gas tank
,
oder
to
).
23 / 120