The internal battery management system (BMS) protects the electronic system and the battery cells. It supports a
continuous current of 135 A. However, it is possible to use higher currents for a limited time, in accordance with the
following values.
Discharging current
150 A
180 A
200 A
NOTICE! Damage hazard
• Do not discharge the battery over the temperature range of -20 °C ... 60 °C.
• If the voltage drops below 10.5 V ± 0.1 V the battery generates an alarm and deactivates the termi-
nals.
13 Cleaning and maintenance
The batteries are maintenance-free.
Occasionally clean the product with a damp cloth.
14 Storing
Before storing, fully charge the battery with a recommended battery charger for 1-2 days.
When the battery is not in use, ensure that the battery voltage does not drop below 12.6 V.
When storing the battery on longer term, completely recharge it every 30 days.
15 Troubleshooting
Problem
Cell voltage high.
Cell voltage low.
16
TLB100/TLB100F
15 min
2 min
60 s
Possible cause
One or more cells with voltage above
the permitted limit.
One or more cells with voltage below
the permitted limit.
Maximum discharging time
TLB120/TLB120F
20 min
3 min
60 s
Suggested remedy
TLB150/TLB150F
20 min
5 min
150 s
Discharge the battery by 3 Ah.
The alarm is deactivated when
the cell voltage returns to normal
operating levels.
Connect a battery charger and
turn on the battery by pressing
and holding the On/Off switch
for 1 second. If the voltage of
one or more cells is below the
safety limit, the battery will re-
main on for about 10 seconds
in order to allow the cells to be
charged and then reset.